CFM Calculator
Enter your room size and target air changes per hour to get the exact airflow your fan needs — with duct friction, elbow losses, air velocity and noise warnings built in. Everything updates live as you type.
Ventilation inputs
Scenario templates
Select a preset to auto-fill common room size and ventilation target.
1Room size
Room volume: 960 cu ft (27.18 m³)
2Ventilation target — air changes per hour
3Duct system
Equivalent round diameter: 6.00 in (152 mm)|Duct area: 28.3 sq in (0.196 sq ft)
Results
Required airflow
96CFM
163 m³/h · 45.3 L/s
Pure ventilation need — room volume × ACH ÷ 60
Next standard size up — delivers ≈ 6.3 ACH in this room.
Duct performance
Comfortably quiet — ideal for bedrooms, bathrooms and living spaces.
Estimates for planning only — verify critical installations against local mechanical code.
What is CFM? The three formulas behind the calculator
CFM (cubic feet per minute) is the volume of air moved by a fan every minute — the standard rating for exhaust fans, range hoods, inline duct fans and HVAC equipment. Every room needs enough airflow to swap its stale air for fresh air a certain number of times each hour, a target called air changes per hour (ACH). Tie the two together and you get the sizing formula this calculator is built on:
Required airflow
CFM = (Area × Height × ACH) ÷ 60
Room volume in cubic feet times the target ACH, divided by 60 minutes per hour. This is the number that sizes the fan.
Reverse check
ACH = (CFM × 60) ÷ Volume
Already own a fan? Divide its CFM × 60 by the room volume to see how many air changes per hour it actually delivers.
Duct velocity
FPM = CFM ÷ Duct area (sq ft)
Air speed inside the duct. Keep it at 600–900 FPM for quiet operation; above 1,200 FPM the duct will be audibly loud.
The 60 in the first formula converts hours to minutes — a room that changes its air 8 times per hour moves its full volume 8 times every 60 minutes, or once every 7.5 minutes. In metric units the same relationship holds with m³/h: multiply the room volume in m³ by ACH (no division needed), and 1 CFM equals 1.699 m³/h or 0.4719 L/s if you need to compare against metric-rated equipment.
Recommended air changes per hour by room type
The ACH you pick drives the whole calculation. The table below collects typical recommended ranges for the most common residential, commercial and industrial spaces. Click any row to load its midpoint into the calculator — then fine-tune for humidity, occupancy and how enclosed the space is.
Residential
| Basements | 3–4 ACH |
| Bedrooms | 5–6 ACH |
| Bathrooms | 6–8 ACH |
| Living rooms | 6–8 ACH |
| Kitchens | 7–8 ACH |
| Laundry room | 8–9 ACH |
| Garage / workshop | 6–20 ACH |
| Attic (if cooling) | 12–15 ACH |
Offices & public
| Business offices | 6–8 ACH |
| Conference rooms | 8–12 ACH |
| Classrooms | 6–20 ACH |
| Hallways | 3–5 ACH |
| Waiting rooms | 4–8 ACH |
| Gymnasiums | 6–10 ACH |
| Malls & retail stores | 6–10 ACH |
| Restrooms | 10–12 ACH |
| Canteens | 7–12 ACH |
| Banks | 4–8 ACH |
| Medical procedure offices | 9–10 ACH |
| Hospital wards | 6–8 ACH |
| Copy / print rooms | 10–12 ACH |
| Computer rooms | 10–14 ACH |
| Lavatories | 6–15 ACH |
| Foyers / lobbies | 8–10 ACH |
| Churches | 8–12 ACH |
| Theatres & auditoriums | 8–15 ACH |
| Swimming pools | 10–15 ACH |
Restaurants
| Dining area | 8–10 ACH |
| Food staging | 10–12 ACH |
| Kitchens (commercial) | 14–60 ACH |
| Bars | 15–20 ACH |
Industrial & special
| Warehouses | 1–2 ACH |
| Machine shops | 6–8 ACH |
| Spray / paint booths | 30–60 ACH |
| Laboratories | 6–10 ACH |
| Hospital facilities | 10–20 ACH |
| Smoking rooms | 15–20 ACH |
| Grow rooms / tents | 20–40 ACH |
| Server rooms | 10–15 ACH |
| Cleanrooms | 10–300 ACH |
| Boiler / compressor rooms | 12–20 ACH |
| Engine / turbine rooms | 12–20 ACH |
| Welding rooms | 15–30 ACH |
| Laundries (commercial) | 15–30 ACH |
| Bakeries | 20–30 ACH |
Ranges are typical industry guidance for planning. Local mechanical codes (such as IMC/ASHRAE 62 standards) govern where they apply — always confirm code-governed spaces with your mechanical designer.
Whole-house ventilation requirements by square footage
Sizing a whole house works differently from sizing one room. Rather than chasing high ACH everywhere, the baseline rule is roughly 1 CFM of continuous ventilation per 50 sq ft of floor area, which lines up with the ASHRAE 62.2 minimum of about 0.35 air changes per hour of outdoor air — or 15 CFM per person. The table below shows the continuous whole-house baseline ventilation that corresponds to common home sizes:
| Home size | Required ventilation |
|---|---|
| Under 500 sq ft | 30–60 CFM |
| 500 – 1,000 sq ft | 45–75 CFM |
| 1,000 – 1,500 sq ft | 60–90 CFM |
| 1,500 – 2,000 sq ft | 75–105 CFM |
| 2,000 – 2,500 sq ft | 90–120 CFM |
| 2,500 – 3,000 sq ft | 105–135 CFM |
| 3,000 – 3,500 sq ft | 120–150 CFM |
| 3,500 – 4,000 sq ft | 135–165 CFM |
| 4,000 – 4,500 sq ft | 150–180 CFM |
| 4,500 – 5,000 sq ft | 165–195 CFM |
Three rules that pair with the table
- Good airflow starts at roughly 1 CFM per square foot when you add spot ventilation into the mix — the classic whole-house rule of thumb.
- Filtering allergens and dust? Aim for the higher end of each range, or at least 5 ACH in the rooms you care about most.
- Larger and more enclosed spaces need proportionally more air changes — the same ACH targets a bigger volume of air.
How to use the CFM calculator
Pick a scenario or start from scratch
The preset cards at the top of the calculator auto-fill a typical room size, an industry-standard ACH (bathroom 8, kitchen hood 15, garage 6, grow tent 30), a matching duct size and a 20% safety factor — all in one click. Prefer manual entry? Just skip the cards.
Enter the room size
Use By Dimensions to type length × width × ceiling height, By Area & Height if you only know the floor area (from a floor plan, for example), or By Volume to enter the total cubic footage straight from a spec sheet. The quick ceiling-height buttons cover the common 8, 9 and 10 ft spans. The room volume updates live so you can sanity-check it.
Set the air changes per hour
Drag the slider or type an exact ACH. If you are unsure, click one of the typical ACH chips or pick a room from the ACH table above. Higher ACH means more fresh air — and a bigger fan.
Add your duct system and read the results
Choose a round duct diameter or rectangular duct width × height (the calculator converts rectangular to its equivalent round diameter automatically). Then open Advanced options to enter the duct run length, count the 90° elbows and pick a safety factor. The results panel shows base CFM, the friction offset, the final recommended airflow, the next standard fan size up, and an air-velocity noise warning for the duct you entered.
Worked example — sizing a bathroom exhaust fan
A full bathroom measures 10 ft × 10 ft with 8 ft ceilings, vented through 25 ft of duct with one 90° elbow. Here is the complete calculation, exactly as the calculator performs it:
| 1. Room volume | 10 ft × 10 ft × 8 ft | 800 cu ft |
| 2. Base airflow (8 ACH) | 800 × 8 ÷ 60 | 107 CFM |
| 3. Duct friction (25 ft) | 25 ÷ 50 × 10% | +5% |
| 4. Elbow loss (1 × 90°) | 1 × 5% | +5% |
| 5. Subtotal with losses | 107 × 1.10 | 117 CFM |
| 6. Safety factor ×1.2 | 117 × 1.2 | 141 CFM |
| 7. Next standard fan size | round up | 150 CFM |
❌ 4-inch duct — too small
A 4" round duct has 12.6 sq in (0.087 sq ft) of area. Pushing 141 CFM through it produces 1,613 FPM — deep into the high-noise zone. The fan will strain against static pressure and the duct will rumble.
✅ 6-inch duct — quiet
A 6" round duct has 28.3 sq in (0.196 sq ft). At 141 CFM the velocity is 717 FPM — comfortably inside the quiet 600–900 FPM band. The same fan, one duct size up, sounds completely different.
This is exactly why the results panel pairs every airflow number with an air-velocity badge: the fan rating and the duct size have to agree. Buy a 150 CFM fan, run 6" duct, and the bathroom hits its 8 ACH target quietly.
Duct size & air velocity chart
The table shows how much airflow a round duct can carry before velocity (and noise) gets out of hand. Target the 600–800 FPM columns for bedrooms and living spaces; up to 1,000 FPM is fine for utility areas.
| Round duct Ø | 600 FPM | 800 FPM | 1000 FPM |
|---|---|---|---|
| 4" (102 mm) | 52 CFM | 70 CFM | 87 CFM |
| 5" (127 mm) | 82 CFM | 109 CFM | 136 CFM |
| 6" (152 mm) | 118 CFM | 157 CFM | 196 CFM |
| 7" (178 mm) | 160 CFM | 214 CFM | 267 CFM |
| 8" (203 mm) | 209 CFM | 279 CFM | 349 CFM |
| 9" (229 mm) | 265 CFM | 353 CFM | 442 CFM |
| 10" (254 mm) | 327 CFM | 436 CFM | 545 CFM |
| 12" (305 mm) | 471 CFM | 628 CFM | 785 CFM |
| 14" (356 mm) | 641 CFM | 855 CFM | 1,069 CFM |
| 16" (406 mm) | 838 CFM | 1,117 CFM | 1,396 CFM |
Noise bands used by the calculator
- ≤ 600 FPM — Quiet. Fan noise fades into the background; ideal anywhere people sleep or relax.
- 600–900 FPM — Normal. The standard residential duct-design range; balanced airflow and sound.
- 900–1,200 FPM — Loud. Audible whoosh; acceptable in laundry rooms and workshops.
- > 1,200 FPM — High noise warning. Whistling and rumble; increase the duct size.
Grow room & tent airflow — the stacked-correction method
Growers size extraction fans the same way the calculator does — volume × ACH ÷ 60 — but with two extra multipliers on top. A healthy crop wants its air fully exchanged at least every 5 minutes (12 ACH), and vigorous gardens typically run every 3 minutes (20 ACH) or faster to manage heat, humidity and CO₂. Divide 60 by the exchange interval you want to get the ACH: every 3 minutes is 20 ACH, every minute is 60 ACH.
Step 1 · Base CFM
volume × ACH ÷ 60
A 4 × 4 ft tent that is 6.5 ft tall holds 104 ft³. At 30 ACH: 104 × 30 ÷ 60 = 52 CFM at the fan.
Step 2 · Duct resistance
× 1.25 (+25%)
Ducting, bends of 30° or more, and long runs all choke the fan. 52 × 1.25 = 65 CFM.
Step 3 · Carbon filter
× 1.25 again (+25%)
Carbon filters and heavily loaded scrubbers add serious drag. 65 × 1.25 = 81 CFM — that is the fan to buy.
Inline duct size chart for grow fans
Once you know the corrected CFM, pick the duct the fan was designed for. This quick-pick chart is the standard recommendation used with inline duct fans in grow tents and greenhouses:
| Fan CFM range | Duct diameter |
|---|---|
| up to 50 CFM | 4" duct (102 mm) |
| 50 – 79 CFM | 5" duct (127 mm) |
| 80 – 119 CFM | 6" duct (152 mm) |
| 120 – 169 CFM | 7" duct (178 mm) |
| 170 – 229 CFM | 8" duct (203 mm) |
| 230 – 299 CFM | 9" duct (229 mm) |
| 300 – 499 CFM | 10" duct (254 mm) |
| 500 – 739 CFM | 12" duct (305 mm) |
| 740 – 1,049 CFM | 14" duct (356 mm) |
| 1,050 – 1,399 CFM | 16" duct (406 mm) |
| 1,400 – 1,874 CFM | 18" duct (457 mm) |
| 1,875 + CFM | 20" duct (508 mm) |
Real-world unit conversions
Many European fan brands rate airflow in m³/h rather than CFM. The exact conversions: 1 CFM = 1.699 m³/h = 28.317 L/min. Going the other way, 1 m³/h = 0.589 CFM and 1 L/min = 0.035 CFM. A 190 m³/h inline fan is therefore about a 112 CFM fan — check the rating before you buy, because a mismatched fan and filter run loud and under-perform.
Target air-exchange chart for industrial spaces
Commercial and industrial ventilation is usually specified the other way around: not air changes per hour, but one full air exchange every N minutes. The two are the same math — ACH = 60 ÷ minutes — and the formula for the fan is:
CFM = Room volume (ft³) ÷ Minutes per exchange
Worked example — warehouse exhaust
A 25 ft × 50 ft warehouse with 15 ft ceilings holds 18,750 ft³ of hot, stale air. Warehouses typically target an exchange every 7 minutes, so: 18,750 ÷ 7 ≈ 2,680 CFM of exhaust. (Large distribution warehouses run the same math per zone — a 25 × 50 × 75 ft high-bay space needs roughly 13,400 CFM.)
Exhaust vs. comfort ratings
Exhaust-focused charts run hotter than comfort-ventilation ACH figures — a warehouse listed at 1–2 ACH for general air quality may still need an exchange every 7 minutes (~8.6 ACH) to dump heat and fumes at the source. Size the exhaust for the load, and supply air to match so the building does not go negative.
Values are common exhaust-fan guidance at 0" static pressure, listed for planning only. Code-governed exhaust (spray booths, commercial kitchens) must follow your local mechanical code and the equipment manufacturer's ratings.
Why getting CFM right matters
Airflow is the one number every part of an HVAC decision hangs on — the fan you buy, the duct you run, the energy bill you pay, and the air quality you breathe. Here is what the calculation actually controls:
Ventilation & air quality
CFM determines how effectively a room's air is replaced with fresh air — removing pollutants, odors, CO₂ and airborne particles. More air changes means fewer contaminants lingering where people live and work.
Temperature control
Adequate CFM distributes conditioned air evenly so hot and cold spots disappear. Too little airflow and a furnace or AC runs continuously without ever equalizing the room.
Equipment sizing
The required CFM is what sizes the fan, range hood, air conditioner, furnace and every register and grille downstream. Get it wrong and every purchase after it is wrong too.
Energy efficiency
Oversized systems short-cycle and waste energy; undersized ones run flat-out and never catch up. Matching CFM to the space keeps runtime — and the bill — at the design minimum.
Humidity & mold control
Stagnant air lets moisture build up on cold surfaces, which is how bathrooms grow mold and crawlspaces rot. Enough CFM to hit 6–8 ACH in wet rooms keeps relative humidity in check.
Preventing wear & tear
Fans forced to push rated CFM through undersized ducts run against high static pressure — overheating motors, shortening bearing life and cycling equipment faster than it was designed for.
CFM per ton — sizing airflow for air conditioning
There is a second, completely different CFM rule in HVAC: cooling delivery. Central air conditioners and heat pumps are sized in tons of cooling, and the blower behind them is sized at about 400 CFM per ton. The standard working range is 350–450 CFM per ton: humid climates run closer to 350 so air spends more time on the cold coil and wrings out moisture, while dry climates run closer to 450 for more sensible cooling.
| Cooling capacity | Blower airflow |
|---|---|
| 1 ton | 400 CFM (at 400/ton) |
| 1.5 tons | 600 CFM (at 400/ton) |
| 2 tons | 800 CFM (at 400/ton) |
| 2.5 tons | 1,000 CFM (at 400/ton) |
| 3 tons | 1,200 CFM (at 400/ton) |
| 3.5 tons | 1,400 CFM (at 400/ton) |
| 4 tons | 1,600 CFM (at 400/ton) |
| 5 tons | 2,000 CFM (at 400/ton) |
Converting CFM to tons (and back)
Divide the blower's airflow by 400 to estimate the cooling tonnage:
Tons ≈ CFM ÷ 400 · CFM ≈ Tons × 400
A blower moving 1,200 CFM is roughly a 3-ton system; a 2.5-ton unit wants about 1,000 CFM across its coil.
AHU CFM calculation — sizing an air handling unit
An air handling unit (AHU) is the blower-and-coil cabinet at the heart of a central AC system, and its airflow uses exactly the CFM-per-ton math above: AHU CFM = cooling capacity (tons) × 400, adjusted within the 350–450 range for humidity. Equipment specified in TR (ton of refrigeration) — the rating you will see across India, the Middle East and much of Asia — converts one-for-one, because 1 TR = 12,000 BTU/h ≈ one standard ton. That gives the quick site rule: 1 TR ≈ 400 CFM.
Worked example — 5-ton AHU
AHU CFM = 5 tons × 400 = 2,000 CFM (≈ 5 TR)
A 5-ton rooftop AHU is specified at about 2,000 CFM across its coil. Compare the fan nameplate against the design number: a unit moving well below its rated CFM points to clogged filters, a fouled coil or slipping belts.
Room AC units — same math, smaller scale
1 TR ≈ 400 CFM · 1.5 TR ≈ 600 CFM · 2 TR ≈ 800 CFM
A 1 TR split or window AC circulates roughly 400 CFM through the room, a 1.5 TR unit about 600 CFM and a 2 TR unit about 800 CFM. That recirculated airflow cools and dehumidifies — the fresh-air ventilation target for the room still comes from the ACH calculation at the top of this page.
Sizing the ducts off an AHU's rated CFM works exactly like the duct size & air velocity chart earlier on this page: keep supply trunks inside the 600–900 FPM quiet band, and give return-air paths about 20–30% more free area than the supply side, since returns run at lower velocity.
Who uses a CFM calculator
HVAC contractors
Size systems, registers, grilles and return paths to the right airflow — and double-check Manual D duct designs against the room-by-room numbers.
Facilities managers
Verify that offices, classrooms and production spaces still meet their air-change targets after renovations, layout changes or complaint investigations.
Growers
Right-size extraction fans, carbon filters and inline ducts for tents and greenhouses where heat and humidity make or break the crop.
DIY homeowners
Pick a bathroom exhaust fan, range hood, garage fan or inline duct fan with confidence — before spending money, not after the bathroom stays damp.
Other meanings of CFM — engines & air compressors
"CFM" shows up in two other worlds with entirely different formulas. Room ventilation has nothing to do with these — but if you landed here from a search, here is the math you are actually after:
🚗 Automotive — carburetor sizing
Carb CFM = (CID × Max RPM × VE) ÷ 3456
An engine's carburetor must flow enough air to feed combustion at peak RPM. The constant 3456 comes from 1,728 cubic inches per cubic foot × 2 — a four-stroke engine only draws in air every second revolution. Volumetric efficiency (VE) is typically 0.7–0.85 for street engines and higher for race builds.
Example: a 350 CID V8 at 6,000 RPM with 0.85 VE needs (350 × 6,000 × 0.85) ÷ 3456 ≈ 517 CFM — so a 500–600 CFM carburetor fits. An undersized carb chokes top-end power; an oversized one bogs at low RPM.
💨 Air compressors — the pump-up test
SCFM = (Tank gal × ΔP) ÷ (14.48 × time, min)
Time how long the compressor takes to fill a known tank from cut-in to cut-out pressure. The formula is (Tank gallons × ΔP) ÷ (7.48 × 14.7 × minutes) — 7.48 gallons per cubic foot, 14.7 PSI per atmosphere.
Example: a 60-gallon tank filling from 40 to 120 PSI in 10 minutes delivers (60 × 80) ÷ (7.48 × 14.7 × 10) ≈ 4.4 SCFM. Within 5–10% of the rated output means the compressor is healthy; a much lower number points to leaks, worn valves, dirty intake filters or slipping belts.
Why the safety factor matters
A fan's rated CFM is measured in free air with no duct attached. Real installations lose flow to filters, exterior hoods, flex-duct corrugation and every bend in the run — a "150 CFM" fan behind 30 ft of flex duct may deliver barely 100. The safety factor (15–20% is standard) buys that loss back on paper before you buy the fan. Combine it with the friction offset for long duct runs and the velocity check for duct size, and the fan you install will deliver the air changes you actually designed for.
Frequently asked questions
What does CFM stand for?▼
CFM stands for cubic feet per minute — the volume of air a fan moves every minute. It is the standard airflow rating for bathroom exhaust fans, kitchen range hoods, inline duct fans, air purifiers and HVAC equipment in North America. A fan rated at 100 CFM moves 100 cubic feet of air each minute, which is 6,000 cubic feet per hour.
How do I calculate CFM for a room?▼
Multiply the room's floor area by the ceiling height to get volume in cubic feet, multiply by the air changes per hour (ACH) the room needs, then divide by 60. For example, a 10 × 10 ft bathroom with 8 ft ceilings has a volume of 800 ft³. At 8 ACH: 800 × 8 ÷ 60 = 107 CFM. The calculator above runs this math instantly, then adds duct friction and a safety factor.
How many CFM per square foot do I need?▼
For general whole-house HVAC, the rule of thumb is 1 CFM per square foot of floor area with standard 8 ft ceilings. Room-specific needs vary a lot: a bathroom needs about 1 CFM per ft² (50 CFM minimum for a typical full bath), while a commercial kitchen needs several times more. Air changes per hour is the more precise method because it accounts for ceiling height, which the per-square-foot rule ignores.
How many air changes per hour does a bathroom need?▼
Aim for 6–8 ACH in a residential bathroom, which is why 8 ACH is the preset in this calculator. For a standard 10 × 10 ft bathroom with 8 ft ceilings that works out to about 107 CFM — right in line with the 80–110 CFM fans most manufacturers sell for full baths. A half bath can drop to 6 ACH; a bathroom with a steam shower deserves 8–10 ACH.
How many ACH should a kitchen or range hood have?▼
A residential kitchen targets 7–8 ACH for general ventilation, but a cooking-range exhaust hood is sized differently: 100 CFM per linear foot of range is the classic rule (so a 30-inch cooktop wants at least 250 CFM), and commercial kitchens run 14–15 ACH or more per code. The Kitchen Hood preset here fills in 15 ACH for hood and commercial applications.
How many CFM does a grow tent need?▼
Grow tents typically need 20–40 air changes per hour to control heat, humidity and CO₂ — this calculator's preset uses 30 ACH. A 4 × 4 ft tent that is 6.5 ft tall holds about 104 ft³, so: 104 × 30 ÷ 60 = 52 CFM at the fan. After adding duct losses and a 20% safety factor you land near 70 CFM, which is why 4-inch inline fans rated 100–190 CFM are so common for 4 × 4 tents.
What size duct do I need for my CFM?▼
Size ducts so air velocity stays between 600 and 900 FPM for quiet residential operation. The capacity table above shows the limits: a 6-inch round duct carries roughly 120–160 CFM quietly, an 8-inch duct about 210–280 CFM, and a 10-inch duct 330–440 CFM. If your fan's CFM pushes velocity above 900 FPM, step up one duct size — the fan will move the same air with far less noise and static pressure.
Why is my exhaust fan so loud?▼
Almost always air velocity. When rated CFM is squeezed through a duct that is too small, too long, or crushed by a kinked flex run, air speed climbs past about 1,000 FPM and the flow starts to whistle and rumble. The fixes are the same three things: a larger duct diameter, fewer and smoother bends, and a shorter duct run. Check the Air Velocity badge in the results panel — above 1,200 FPM the noise will be obvious.
How do duct length and elbows affect the CFM I need?▼
Every foot of duct and every bend adds static pressure that chokes the fan below its free-air rating. This calculator adds 10% for every 50 feet of duct and 5% for each 90° elbow — so a 50 ft run with two elbows needs about 20% more fan than the bare-room number. Flexible corrugated duct is worse than smooth metal: expect it to eat most of a 10–20% margin on its own.
Should I use round or rectangular duct?▼
Round duct is more efficient — it has the least perimeter for a given area, so less friction. When a rectangular duct must fit inside a wall or ceiling joist bay, use the equivalent diameter the calculator computes: De = 1.3 × (w·h)^0.625 / (w+h)^0.25 (the ASHRAE formula). A 3.25 × 10 in wall stack is equivalent to a 6-inch round — but only at equal friction, so a size-for-size rectangular swap of a round duct will under-perform.
What is a safety factor in CFM calculations, and do I need one?▼
A safety factor pads the calculated CFM for real-world losses the formula cannot see: dirty filters, clogged exterior hoods, slight duct compression, and the gap between a fan's rated flow and its installed flow. 15–20% is standard practice, so pick ×1.15 or ×1.2 once you have ducting installed. Skipping it means the fan you install will almost always deliver fewer air changes than you designed for.
How do I convert CFM to m³/h or L/s?▼
Multiply CFM by 1.699 to get cubic meters per hour, or by 0.4719 to get liters per second. Going the other way, divide m³/h by 1.699 or L/s by 0.4719. For example, a 100 CFM bathroom fan equals 170 m³/h or 47 L/s. Switch the calculator to metric and every result is shown in m³/h and L/s automatically.
How many CFM do I need for a 2,000 square foot house?▼
It depends on ceiling height and the target ACH. A 2,000 sq ft home with standard 8 ft ceilings holds about 16,000 ft³ of air. At 6 ACH that is 16,000 × 6 ÷ 60 = 1,600 CFM for the whole house, and at 8 ACH it rises to about 2,133 CFM. Whole-house ventilation is normally delivered room by room, so the whole-house table above shows the continuous baseline ventilation recommended for each home size.
How much ventilation is required per person?▼
ASHRAE 62.2, the residential ventilation standard, calls for roughly 15 CFM of outdoor air per person plus a small rate per square foot — which works out to at least 0.35 air changes per hour of outdoor air for a typical home. For a family of four, plan on around 60 CFM of continuous fresh-air supply before you count any spot ventilation from bathroom or kitchen exhaust fans.
How many CFM per ton of air conditioning do I need?▼
The standard is about 400 CFM per ton of cooling, with a working range of 350–450. Humid climates run closer to 350 CFM per ton so the coil dehumidifies more, while dry climates run closer to 450. To convert the other way, divide the system airflow by 400: a 1,200 CFM blower is roughly a 3-ton system. Note this sizes cooling delivery — it is separate from the ventilation CFM the calculator above computes.
Can a room have too much CFM?▼
Yes. Oversizing causes drafty registers, whistling grilles, higher energy bills, and poor humidity control — in air conditioners, airflow that is too fast can actually leave moisture in the air because air passes over the cold coil before it can condense and drain. Excess CFM can also short-circuit ventilation, pulling fresh air straight to the exhaust before it has mixed with room air. Match the CFM to the room's purpose instead of assuming bigger is better.
What is the difference between CFM and SCFM?▼
CFM is the volume of air moved at the actual conditions where it is measured, while SCFM (standard cubic feet per minute) is normalized to standard conditions — typically sea-level pressure and 68–70 °F. Compressor output is usually quoted in SCFM so different units can be compared fairly; a pump-up test result in SCFM may read slightly lower than the compressor's nominal CFM rating at altitude or high temperature.
How do carbon filters affect grow room CFM?▼
A carbon filter inline on the duct run adds meaningful resistance, and scrubbing odor also depends on keeping air speed inside the filter's rated range. The common grow-room practice is to multiply the base CFM by 1.25 for duct resistance, then by another 1.25 if you run a carbon filter or unusually long or bendy ducting — a combined 56% bump. See the grow room section above for a full worked example.
What CFM carburetor do I need for my engine?▼
Engine airflow uses a different formula: carb CFM = (engine size in cubic inches × max RPM × volumetric efficiency) ÷ 3456. A 350 cubic-inch V8 spinning to 6,000 RPM with 0.85 volumetric efficiency needs about (350 × 6,000 × 0.85) ÷ 3456 ≈ 517 CFM. This has nothing to do with room ventilation — it is a separate automotive use of the CFM unit covered in the section above.
How do you calculate CFM for an AHU (air handling unit)?▼
Multiply the unit's cooling capacity by 400 CFM per ton: AHU CFM = tons × 400, adjusted within the 350–450 CFM-per-ton range for humidity. A 5-ton AHU therefore delivers about 2,000 CFM, and a 10-ton unit about 4,000 CFM. If the spec sheet lists capacity in TR (tons of refrigeration), the math is identical because 1 TR equals one standard ton — so a 15 TR air handler moves roughly 6,000 CFM. Compare the nameplate airflow against the design value: a large gap usually means clogged filters, a fouled coil or duct restrictions.
How many CFM does a 1 TR air conditioner move?▼
About 400 CFM. One TR (ton of refrigeration) equals 12,000 BTU/h of cooling — the same as one standard ton — and blowers are sized at roughly 400 CFM per ton. So a 1 TR split or window AC circulates about 400 CFM through the room, a 1.5 TR unit about 600 CFM and a 2 TR unit about 800 CFM. Remember this is recirculated air that cools and dehumidifies; the fresh-air ventilation target for the room still comes from its ACH requirement.
More Tools for Airflow & Ventilation
Purpose-built companions to the CFM calculator — each one does a single job end to end.
Air Handler CFM Calculator
Air handler CFM calculator: split supply vs return air, check filter face velocity at 300–625 FPM, size return grilles at 350–500 FPM, and see CFM per ton.
Open calculatorEngine CFM Calculator
Engine CFM calculator: size carburetors from CID and RPM with VE, correct for boost pressure, match throttle bodies up to 102 mm, and pick radiator fan CFM.
Open calculatorGreenhouse CFM Calculator
Greenhouse CFM calculator: summer cooling at one exchange per minute, winter 2–3 ACH, HAF circulation fans, and evaporative pad pairing for any size greenhouse.
Open calculatorBathroom Exhaust Fan CFM Calculator
Bathroom exhaust fan CFM calculator: size by room volume at 8 ACH, 1 CFM per sq ft, or the 50 CFM fixture rule — plus duct corrections and sone noise.
Open calculatorAir Changes per Hour Calculator
Convert air changes per hour to CFM and back with the ACH formula — room-by-room ACH standards, worked examples, and why delivered airflow beats nameplate.
Open calculatorCFM to Square Feet Calculator
Turn CFM into square feet: coverage area from 700, 1500 or 3300 CFM at 0.5–3 CFM per ft², with ceiling-height corrections and device coverage charts.
Open calculatorMore Guides
Deep-dive references that explain the numbers behind the calculators — sizing rules, standards and real-world examples.
Size the fan once — breathe easy for years
Thirty seconds of measuring beats a bathroom that never dries out. Run your numbers, check the velocity badge, and pick the fan size the calculator recommends before you order.
Back to the calculator