Finishing & Lab Exhaust

Paint Booth CFM Calculator — Spray Booth & Fume Hood Airflow

One paint booth CFM calculator for both vocabularies: spray booths sized at 100 FPM cross-draft or 50–75 FPM downdraft, and fume hoods at 80–100 FPM over the sash opening — same physics, velocity × open area, with fan and makeup-air matching built in.

Booth & hood airflow panel

Pick the enclosure

Face velocity × open area

Open area70.0 sq ft
Design velocity100 FPM
Required exhaust7,000 CFM
Exhaust duct 24"2,228 FPM ✓

Exhaust fan motor class

2.7

HP @ 1.5 in. w.c. · air HP 1.65

Makeup air to supply

7,000

CFM replacement — 90–100% of exhaust

Checkpoint: booth fans must be spark-resistant with the motor out of the airstream — sizing is the math; the listing is the law.

Booth CFM is one entry in a bigger toolkit: for general room sizing by air changes per hour, the free online CFM calculator does the baseline job in seconds, and the CFM calculator toolset indexes every specialty page — hoods, fans, ducts and more — in one place.

The scenario cards

Three enclosures, one dial

Every enclosure on this page is a face-velocity machine: the air moves through an opening at a design speed, and the CFM is simply that speed times the opening’s area. What changes between cards is which area you measure and which band the speed sits in:

Cross-draft booth

100 FPM

CFM = width × height × 100

+ Cheapest to build and service; air travels front-to-back past the operator.

− Overspray rides the airstream across the work — filtration pads load fast.

Downdraft booth

50–75 FPM

CFM = length × width × 50–75

+ Overspray falls away from the part and the painter — the cleanest finish environment.

− Needs a pit or raised floor and the largest fans; the most expensive build.

Lab fume hood

80–100 FPM

CFM = sash width × opening height × 80–100

+ Containment tested at the sash; constant-volume or VAV exhaust both work.

− Face velocity collapses as the sash opens wide — CFM must follow the opening.

💡 Read the numbers side by side

A 10 × 7 ft opening at 100 FPM (cross-draft), a 10 × 20 ft floor at 60 FPM (downdraft), and a 4 × 1 ft sash at 90 FPM (hood) produce 7,000, 12,000 and 360 CFM respectively. The velocity band is small; the area is what scales — which is why booths are big-ticket ventilation and hoods are branch-sized.

Booth size tables, ready to quote

The two most common shop booths, pre-computed. Fan motor class assumes a 1.5 in. w.c. exhaust-path budget at 62% fan efficiency:

Cross-draft booths @ 100 FPM

Booth openingAreaCFM @ 100 FPMFan class
6 × 6 ft36 sq ft3,600 CFM1.4 HP
8 × 7 ft56 sq ft5,600 CFM2.1 HP
10 × 7 ft70 sq ft7,000 CFM2.7 HP
10 × 8 ft80 sq ft8,000 CFM3.0 HP
12 × 8 ft96 sq ft9,600 CFM3.7 HP
14 × 9 ft126 sq ft12,600 CFM4.8 HP

Downdraft booths @ 50 / 60 / 75 FPM

Floor footprint@ 50 FPM@ 60 FPM@ 75 FPM
12 × 8 ft4,800 CFM5,760 CFM7,200 CFM
16 × 9 ft7,200 CFM8,640 CFM10,800 CFM
20 × 10 ft10,000 CFM12,000 CFM15,000 CFM
24 × 12 ft14,400 CFM17,280 CFM21,600 CFM
30 × 14 ft21,000 CFM25,200 CFM31,500 CFM
Automotive spray booth interior with fresh filters and bright even lightingClean finishes start with a clean air streamPhoto: Unsplash

Fume hood CFM: the sash is the variable

A lab hood’s opening changes every time the sash moves, so its fume hood CFM calculation is a family of answers, not one. The band: 80–100 FPM across the sash plane. The sizing decision is between a constant-volume hood (sized at full open, always exhausting) and a VAV hood (modulating, sized to hold velocity):

Sash widthOpening @ 1 ft@ 80 FPM@ 90 FPM@ 100 FPMFull open @ 2.5 ft
3 ft sash3 sq ft240 CFM270 CFM300 CFM750 CFM
4 ft sash4 sq ft320 CFM360 CFM400 CFM1,000 CFM
5 ft sash5 sq ft400 CFM450 CFM500 CFM1,250 CFM
6 ft sash6 sq ft480 CFM540 CFM600 CFM1,500 CFM
8 ft sash8 sq ft640 CFM720 CFM800 CFM2,000 CFM

✓ VAV in one paragraph

A VAV hood holds 90 FPM at whatever the sash is by modulating the exhaust — 4 ft sash at 1 ft open pulls ~360 CFM, fully open ~900. Sash discipline is the energy strategy: a lab that keeps sashes low cuts hood exhaust (and its heated or chilled makeup air) by half or more without touching containment.

⚠️ The velocity ≠ containment trap

Past roughly 120–130 FPM, face velocity stops improving containment and starts creating turbulence that pulls vapor back out of the hood. Chasing “more FPM is safer” is the classic misreading — the band exists because both edges of it fail: too slow spills, too fast stirs.

🛠 Scope note: capture hoods over cooktops follow a completely different sizing rule — linear feet and kitchen air changes, not face velocity. That job belongs to the range hood CFM calculator; this page stays with finishing booths and laboratory sashes.

The fan, the duct, and the air you must give back

CFM is the middle of a three-part system. The exhaust fan must deliver the CFM against real resistance, and the building must hand back every cubic foot — heated, in winter:

1 · Fan

CFM at true static

Budget the exhaust path: intake filters + exhaust pads 0.3–0.6 in. w.c. clean (to 1.5 loaded), duct 0.2–0.5. Motor HP = CFM × SP ÷ 6,356 ÷ fan efficiency — the panel computes it live.

2 · Duct

1,200–3,000 FPM

Booth exhaust carries no chips; moderate velocity wins. The duct check in the panel flags sizes outside the band — undersized ducts strangle the fan exactly like any other system.

3 · Makeup air

90–100% of exhaust

Unreplaced air depressurizes the building and stalls the booth. Supply it close to the booth, tempered in cold climates — the makeup-air unit is often half the installed cost.

💡 Filter loading is a schedule you can measure

A manometer across the filter bank turns “the booth seems weaker” into a number: when the pressure delta doubles from its clean reading, the pads are due. Booths that keep velocity with loaded filters do it by moving less air — the velocity gauge lies unless the filter budget is honest.

Spray booth & fume hood FAQ

TopHow do I use a paint booth CFM calculator?▼

Pick the booth style, measure the opening the air moves through, and multiply by the design face velocity. A cross-draft booth that is 10 ft wide with a 7 ft opening moves 10 × 7 × 100 = 7,000 CFM. A downdraft booth is sized on its floor footprint instead — 10 × 20 ft at 60 FPM wants 12,000 CFM. A fume hood is sized on the sash opening: a 4 ft sash opened to 18 inches at 90 FPM needs 540 CFM. Same physics in all three: velocity × open area = CFM.

How is CFM calculated for a spray booth?▼

Cross-draft: CFM = booth width × height × 100 FPM — the classic face-velocity rule that keeps overspray and solvent vapor moving away from the operator at a pace that captures but does not turbulently stir the mist. Downdraft: CFM = floor length × width × 50–75 FPM, applied across the pit or filter floor because air travels straight down rather than across. After the raw CFM, add the exhaust-path losses — booth filters (0.3–0.6 in. w.c. clean, up to 1.5 as they load) and duct — then pick the fan for the CFM at that resistance.

Why 100 FPM for cross-draft booths and less for downdraft?▼

Because geometry does part of the work. In cross-draft, 100 FPM is the speed at which the airstream carries overspray past the part without eddying back — slow enough to keep the fog controlled, fast enough to sweep it. Downdraft air only has to fall: gravity assists, so 50–75 FPM achieves the same containment with less energy and less turbulence at the part. Pushing downdraft booths to 100+ FPM wastes fan power and can actually disturb the coating by driving air past the surface too briskly.

How is CFM calculated for a fume hood?▼

CFM = sash opening area × face velocity, with 80–100 FPM the standard containment band for general chemistry hoods. A 4 ft hood with the sash at 12 in. (1 ft) open is 4 sq ft; at 90 FPM that is 360 CFM. The critical detail: the sash area changes every time someone moves it, so constant-volume hoods are sized at full open — a 4 ft sash fully raised to 30 in. needs 900 CFM continuously — while VAV systems modulate exhaust to hold velocity as the sash moves, cutting lab energy use by half or more.

What size fan does a paint booth need?▼

Size the fan for the booth's CFM at its true static pressure, not free air. A cross-draft booth's exhaust path includes intake filters, exhaust pads and duct: budget roughly 1.0–2.0 in. w.c. total. A 7,000 CFM booth at 1.5 in. w.c. needs an air horsepower of 7,000 × 1.5 ÷ 6,356 ≈ 1.65, so a real fan with 60–65% efficiency wants about a 2.5–3 HP motor. Booth fans must also be spark-resistant construction with the motor out of the airstream — a listing requirement, not a preference.

Why does a paint booth need makeup air?▼

Every CFM exhausted must be replaced, or the booth goes negative and starts starving. An un-maked-up booth depressurizes the building, drags cold winter air through every door and crack, stratifies the booth itself, and can stall the fan's delivered CFM well below rating. The makeup-air unit supplies 90–100% of exhaust CFM, tempered in cold climates — a 7,000 CFM booth in a Michigan winter is also a 7,000 CFM heater problem, which is why makeup-air sizing is part of the booth decision, not an afterthought.

How often do booth filters change the CFM math?▼

Continuously, in one direction: filters load, resistance rises, delivered CFM falls. Intake pads and exhaust pads start near 0.3–0.6 in. w.c. clean and climb toward 1.0–1.5 loaded. A fan chosen with no margin reads low within weeks; a manometer across the filter bank is the cheap instrument that turns guesswork into a schedule — when the delta doubles, swap the pads. This is the same loading physics a dust collector's baghouse shows, and the same fix: monitor the resistance, not the calendar.

What duct size carries booth exhaust air?▼

Booth exhaust moves at moderate velocity — 1,500–2,500 FPM is the usual design band, because paint overspray that reaches the duct is either captured at filters or is vapor, and there is no chip-transport duty. A 7,000 CFM booth at 2,000 FPM needs 3.5 sq ft of duct — about a 26-inch round, or a box plenum of equivalent area. Fume hood exhaust is similar at 1,000–2,000 FPM, sized by lab design and corrosion/condensate considerations rather than transport velocity.

Is a kitchen hood the same calculation as a paint booth?▼

The physics overlaps — both move air through a capture opening — but the sizing inputs are entirely different. Kitchen hoods are sized by cooktop linear feet or by kitchen air changes, with grease handling and makeup air as the governing constraints; spray booths and fume hoods are sized by face velocity over an opening. If you landed here while planning a kitchen, the range hood CFM calculator handles that job with the right rules; this page stays with finishing and lab exhaust.

Can one calculator cover both spray booths and fume hoods?▼

Yes — deliberately. Both devices are 'velocity × open area' machines, and the shared formula is the insight most sizing guides bury: a cross-draft booth at 100 FPM, a downdraft at 50–75, and a hood sash at 80–100 are three settings of one dial. The card you select changes which area you measure and which velocity band applies; everything downstream — CFM, fan, static budget, makeup air — follows identically. One page, two vocabularies, zero repeated math.

Related Tools & Guides

🌀

CFM to FPM Calculator

Convert CFM to FPM and FPM to CFM for any round or rectangul...

🔄

CFM Conversion Calculator

Convert CFM to m³/h, CMH, CMM, L/s, LPM, m³/s and CFH instan...

🔥

CFM to BTU Calculator

Convert CFM to BTU and BTU to CFM with the 1.08 ΔT formula —...

⚙️

Fan Performance Calculator

Calculate fan CFM from RPM with the affinity laws — static p...

🍳

Range Hood CFM Calculator

Free range hood CFM calculator: size kitchen hoods by cookto...

☀️

Attic Fan CFM Calculator

Attic fan CFM calculator: size attic exhaust at 0.7–1.0 CFM ...

🔧

Air Compressor CFM Calculator

Air compressor CFM calculator: total your tools' CFM at 90 P...

🌡️

SCFM to CFM Calculator

SCFM to CFM calculator with pressure and temperature correct...

🌀

Blower CFM Calculator

Blower CFM calculator: size any blower from wheel diameter, ...

🌱

Grow Tent CFM Calculator

Grow tent CFM calculator: size 2×2 to 4×8 tents by air chang...

❄️

CFM per Ton Calculator

CFM per ton calculator: convert tons to CFM at 350, 400 or 4...

🪵

Dust Collector CFM Calculator

Dust collector CFM calculator: match machine CFM demands, ke...

🌫️

Air Purifier CFM Calculator

Air purifier CFM calculator: match CADR to room size with th...

💧

Evaporative Cooler CFM Calculator

Evaporative cooler CFM calculator: size swamp coolers at 20–...

🌬️

Air Handler CFM Calculator

Air handler CFM calculator: split supply vs return air, chec...

🏎️

Engine CFM Calculator

Engine CFM calculator: size carburetors from CID and RPM wit...

🌿

Greenhouse CFM Calculator

Greenhouse CFM calculator: summer cooling at one exchange pe...

🚿

Bathroom Exhaust Fan CFM Calculator

Bathroom exhaust fan CFM calculator: size by room volume at ...

🔁

Air Changes per Hour Calculator

Convert air changes per hour to CFM and back with the ACH fo...

📐

CFM to Square Feet Calculator

Turn CFM into square feet: coverage area from 700, 1500 or 3...

🏡

Whole House Fan CFM: Sizing Whole-House Fans, HRVs & ERVs

Size a whole-house fan at 2–3 CFM per sq ft or one air chang...

Velocity in, CFM out — booth or hood

Pick the enclosure, feed it the opening, and walk away with exhaust CFM, fan class, duct verdict and the makeup-air number.