Kitchen & Commercial Hoods

Range Hood CFM Calculator — Kitchen & Commercial Sizing

A range hood CFM calculator that runs both home methods at once — the 100 CFM per linear foot capture rule and the kitchen-size ACH method — then adds what most tools skip: island and pro-style uplifts, commercial footprint sizing, the right duct for a 600 CFM hood, and the 400 CFM makeup-air threshold.

Range hood sizing dashboard

Step 1 — describe the kitchen

Step 2 — pick the hood type

Mounted against a wall with a backsplash — the plume is easiest to capture, so the base 100 CFM per linear foot applies.

Both home methods compared

Capture rule (100 CFM × 3.0 ft)300 CFM
Kitchen ACH (15 ACH, 1,296 ft³)324 CFM

The larger method wins: the ACH method governs — a big or tall kitchen demands more than the cooktop does.

Buy this size (stocked)

400

CFM · use a 7 in. round round duct

⚠️ Makeup air flagged (≥ 400 CFM): IRC M1503.6 requires a makeup-air damper sized within ~10% of the exhaust, and a dedicated 15 A circuit is standard practice for the hood and the damper motor.

Checkpoint: hood width should match or exceed the cooktop, and the mounting height does the rest of the work — no CFM number can rescue a hood hung 40 inches above the burners.

The rules, face to face

100 CFM per linear foot vs kitchen size: which rule answers to “how to calculate CFM for a range hood”?

Every kitchen exhaust CFM calculator online leans on one of two rules, and they measure different things. The capture rule sizes the fight between the hood and the hot plume rising off the burners. The kitchen ACH method sizes the room itself — how much air a kitchen of your floor area and ceiling height should turn over. A hood that wins the plume fight in a tiny galley can still leave a 12-foot ceiling full of steam; the honest answer is whichever number is larger. The matrix puts every rule side by side:

Sizing ruleWhat it assumesWorked resultBest forVerdict
100 CFM per linear footWall hood, standard 24–30 in. mounting, moderate burner output36 in. cooktop → 300 CFMEveryday home cooking on a wallOptimal for homes
120 CFM per linear foot (island)Hood open on all sides; cross-drafts steal part of the plume36 in. island cooktop → 360 CFMIsland hoods, open-plan kitchensOptimal for homes
150 CFM per linear foot (pro-style)60,000+ BTU ranges throwing a hot, fast plume48 in. pro range → 600 CFMHigh-output ranges, wok cookingCross-check
Kitchen ACH method (15 ACH)The kitchen needs general exhaust, not just plume capture144 sq ft × 9 ft → 324 CFMCross-checking the capture rule in big or tall kitchensCross-check
Commercial footprint ruleCanopy over a full cooking line; grease-rated ductwork35 sq ft canopy → 3,500–5,250 CFMRestaurants and heavy-duty linesCode-heavy territory

💡 Why islands pay 20% more

A wall hood has a backsplash that walls in the rising plume; an island hood fights drafts from every seat in the room. Wind-tunnel testing of capture efficiency is why the guideline steps from 100 to 120 CFM per foot — and why island hoods should be 3–6 inches wider than the cooktop on every open side.

⚠️ The mounting-height trap

CFM and height are a package deal. Hang a 400 CFM hood 42 inches up and its effective capture falls by a third; the same hood at 26 inches over an electric cooktop captures like a bigger machine. The calculator’s number assumes 24–30 inches over electric and 27–36 over gas.

❌ Don’t: buy CFM instead of capture

A shallow 15-inch-deep hood at 900 CFM loses to a 24-inch-deep hood at 400 CFM over the same range. Capture geometry — depth, width, height — beats raw airflow every time a plume escapes the hood’s envelope.

A modern kitchen with a stainless steel range hood over a professional cooktopCapture geometry first, CFM secondPhoto: Unsplash

Kitchen hood CFM calculation, worked four ways

The same three kitchens, computed by hand so you can audit the dashboard. Each row is the exact arithmetic the calculator runs:

Small galley kitchen, wall hood

Cooktop30 in. = 2.5 linear ft
Capture rule2.5 × 100250 CFM
ACH method(70 sq ft × 8 ft × 15) ÷ 60140 CFM
Buylarger, stocked250–300 CFM · 6 in. duct

Family kitchen with island cooktop

Cooktop36 in. = 3.0 linear ft, island
Capture rule3.0 × 120360 CFM
ACH method(168 sq ft × 9 ft × 15) ÷ 60378 CFM
Buylarger, stocked400 CFM · 7 in. duct · just under the makeup-air line

Pro-style range, tall great room

Cooktop48 in. = 4.0 linear ft, pro-style
Capture rule4.0 × 150600 CFM
ACH method(300 sq ft × 10 ft × 15) ÷ 60750 CFM
Buylarger, stocked750–900 CFM · 10 in. duct · makeup air + dedicated circuit required
⚠️ Where ACH and capture disagree badly: if the ACH number is more than about double the capture number, the kitchen is very large or very tall for the cooktop — buy the hood for the cooktop, and treat the difference as a whole-room ventilation job (a quiet continuously running exhaust) rather than oversizing a hood nobody runs on high.

Commercial kitchen hood CFM: 100–150 CFM per square foot of hood

A commercial kitchen exhaust hood CFM calculator plays a different sport. Restaurant canopies are sized from the hood’s own footprint because the hood must swallow the combined plume of a whole line, not one cooktop. The standard planning band:

CFM = hood area (sq ft) × 100 (light duty) … 150 (heavy duty)

Light duty: electric ranges, ovens, steamers · Heavy duty: gas ranges, broilers, woks, salamanders

Canopy (L × D)AreaLight duty (100)Heavy duty (150)Also required
8 × 3.5 ft28 sq ft2,800 CFM4,200 CFMGrease duct · fire suppression · ~85% makeup air
10 × 3.5 ft35 sq ft3,500 CFM5,250 CFMGrease duct · fire suppression · ~85% makeup air
12 × 4 ft48 sq ft4,800 CFM7,200 CFMGrease duct · fire suppression · ~85% makeup air
16 × 4.5 ft72 sq ft7,200 CFM10,800 CFMGrease duct · fire suppression · ~85% makeup air
⚠️ Commercial is a code conversation: type-I grease hoods carry requirements for duct slope, access panels, UL-listed suppression and interlocked makeup air that no calculator can settle. Use the footprint numbers to bracket the mechanical design, then let a kitchen-exhaust contractor and your local mechanical inspector finalize the spec.

The 600 CFM duct-size question (and every other size)

The classic search — “600 CFM range hood pipe size calculator” — has a stable answer because hood ducts are sized to keep velocity in the quiet 900–1,800 FPM band. Below that, air lumbers and grease settles; far above it, the duct whistles and the motor loses flow to friction. The table is the whole answer:

Hood CFM (up to)Round ductVelocity at ratingRectangular equivalent
250 CFM6 in. round≈ 1,275 FPM at 6 in.3¼ × 10 in. wall stack
400 CFM7 in. round≈ 1,500 FPM at 7 in.3¼ × 12 in. wall stack
600 CFM8 in. round≈ 1,720 FPM at 8 in.3¼ × 14 in. wall stack (tight)
900 CFM10 in. round≈ 1,650 FPM at 10 in.6 × 10 in. joist-bay duct
1,500 CFM12 in. round≈ 1,910 FPM at 12 in.6 × 10 in. joist-bay duct

💡 One size up on long runs

Under about 15 feet with one elbow, the table stands as-is. Past 20 feet or two 90° bends, step up one duct size — the fan you bought keeps its rated CFM instead of surrendering 15–25% of it to friction. For exact equivalent diameters of any rectangle, the CFM to FPM calculator checks the velocity either way.

❌ Never neck down, never flex

A 6-inch flex duct on a 600 CFM hood is the single most common installer shortcut and it costs more than it saves: corrugated walls alone add 20–30% friction. Smooth-wall rigid round duct of the table size, as few elbows as the route allows, and a wall cap with a backdraft damper — that is the whole recipe.

Round rigid ductwork and elbows installed above a kitchen ceiling for a range hood runRigid round duct, sized once, sized rightPhoto: Unsplash

400 CFM: where makeup air (IRC M1503.6) and the dedicated circuit enter

“400 CFM” is the most searched number in hood sizing because it is the line where a kitchen appliance becomes a whole-house air system. Exhaust more than 400 CFM from a tight home and the house goes negative: the hood starts pulling replacement air down chimneys, back through atmospherically vented water heaters, and through every gap in the envelope. That is why the IRC’s M1503.6 provision requires makeup air for exhaust over 400 CFM — a motorized damper, usually interlocked with the hood, admitting roughly as much air as the hood removes.

1. The thresholdHood or exhaust over 400 CFMMakeup air required
2. The sizingMakeup air ≈ exhaust −10%600 CFM hood → ≥ 540 CFM damper
3. The deliveryMotorized damper, interlocked or manual switchDucted to living space or HVAC return
4. The electricalHood on dedicated 15 A/120 V circuitDamper gets its own circuit too
5. The alternativeStay ≤ 400 CFM, recirculating modeNo makeup air, but no exhaust either

The electrical load, in plain numbers

A typical 30–36 inch hood draws 1–2.5 A (light, blower, controls) — trivially inside a 15 A circuit, but sharing one with a microwave or two countertop appliances invites nuisance trips at dinner time. Pro-style remote blowers add a second motor (0.5–1.5 A) and makeup-air dampers add a third small load. Two dedicated 15 A circuits cover the whole assembly with margin; that is the “dedicated circuit” line electricians actually mean.

💡 The cheap alternative

If the kitchen layout cannot accept a makeup-air duct, a hood with a genuinely variable blower changes the math: a 600 CFM-max hood running at 350 CFM for daily cooking stays under the threshold, with the makeup-air system only relevant for the rare full-power run. Check how the damper interlock is implemented in your jurisdiction before relying on this.

Grill CFM: outdoor BBQ hoods and the wind problem

An outdoor grill hood looks like a pro-style residential hood and is sized the same way — 150 CFM per linear foot as the floor — with two outdoors penalties that push planning numbers toward 200 CFM per linear foot:

Cross-breezes

Sizing driver

Open patios generate drafts no indoor kitchen sees. A 10 mph breeze across a 42-inch grill shoves the plume sideways; deeper hoods (24 in.) and higher CFM buy the capture back.

Mounting height

Geometry

Outdoor hoods hang 30–36 in. above the grill — taller than indoor — because of headroom over open flames. Every inch of extra height needs extra CFM to close the gap.

Duct run reality

Installation

Outdoor island installs often route 15–25 ft to above the roofline. Size the duct one step up from the table and keep the run rigid — flex outdoors sags and pools grease.

Built-in grill widthFloor (150 CFM/ft)Windy-patio target (200 CFM/ft)Buy (stocked)
32 in. (2.7 ft)400 CFM533 CFM600 CFM
36 in. (3.0 ft)450 CFM600 CFM600 CFM
42 in. (3.5 ft)525 CFM700 CFM750 CFM
54 in. (4.5 ft)675 CFM900 CFM900 CFM

Where this page ends and the homepage begins

The homepage’s Kitchen Hood preset is deliberately simple: 15 ACH on any room volume with an 8-inch duct and the standard safety factor — the right tool for a two-minute answer and for rooms that are not kitchens. This page is the hood specialist: the capture rules that override ACH, the island and pro-style uplifts, commercial footprint sizing, the duct table, the 400 CFM makeup-air line and the grill-hood variants. Two related jobs live elsewhere: the homepage ACH table keeps the room-by-room baselines, and the fan performance calculator predicts what an already-installed hood delivers on a long, restrictive duct run.

Range hood CFM FAQ

TopHow do I use a range hood CFM calculator?▼

Enter the cooktop width, the kitchen's floor area and ceiling height, and pick the hood type. The calculator runs both residential methods at once — the 100 CFM per linear foot capture rule and the kitchen-area ACH method — and shows the larger result as the number to shop against, plus the duct size and the 400 CFM makeup-air flag. A 36-inch wall hood in a 144 sq ft kitchen lands at 300 CFM by capture and 324 CFM by ACH: buy the 400 CFM hood, not the 300.

How to calculate CFM for a range hood from kitchen size?▼

The kitchen-size (ACH) method multiplies the room's volume by 15 air changes per hour and divides by 60: CFM = (area × ceiling height × 15) ÷ 60. A 12 × 12 ft kitchen with 9 ft ceilings holds 1,296 ft³, so 1,296 × 15 ÷ 60 = 324 CFM. This method sizes the room's general exhaust; the linear-foot method below sizes the hood's capture ability — use whichever result is larger.

How to calculate CFM for a kitchen hood by linear feet?▼

Measure the cooking surface front-to-back or side-to-side in feet and multiply by 100 CFM for a wall-mounted hood, 120 for an island, or 150 for a pro-style range with high-BTU burners. A 36-inch (3 ft) wall cooktop therefore needs 300 CFM; the same cooktop on an island needs 360 CFM. This is the capture rule — it assumes the hood is the right width and hangs at the right height (24–30 in. above an electric cooktop, 27–36 in. above gas).

How is commercial kitchen hood CFM calculation different?▼

Commercial canopy hoods are sized by hood footprint, not cooktop width: 100 CFM per square foot of hood area for light-duty (electric) appliances and up to 150 CFM per square foot for heavy-duty gas ranges and broilers. A 10 ft × 3.5 ft canopy over a heavy-duty line is 35 sq ft × 100–150 = 3,500–5,250 CFM. Commercial exhaust also triggers fire suppression, grease ducts and makeup-air interlocks — this calculator sizes the airflow, and your local mechanical code governs the rest.

How do you calculate CFM for commercial kitchen exhaust ventilation?▼

Two routes are accepted for canopy hoods: the footprint rule above, and the linear-foot rule for wall-mounted canopies — roughly 200–300 CFM per linear foot of heavy-duty cooking line. The exhaust must be balanced by makeup air of about 80–90% of the exhaust volume, or the kitchen goes negative and doors become hard to open. The dashboard's commercial panel computes the footprint band so you can bracket the spec before a kitchen designer quotes it.

What pipe size does a 600 CFM range hood need?▼

600 CFM wants an 8-inch round duct at a working velocity near 1,720 FPM — inside the quiet 900–1,800 FPM band for short runs. If the run is longer than about 20 feet or has more than two elbows, step up to 10-inch, because every extra foot of duct adds back-pressure that a fixed-speed hood motor pays for in lost flow. A 6-inch duct on a 600 CFM hood pushes velocity past 3,000 FPM: loud in the kitchen and 15–25% flow loss at the hood.

Why does 400 CFM trigger a makeup air requirement?▼

Under IRC M1503.6, exhaust hoods rated over 400 CFM must be provided with makeup air — a motorized damper that admits replacement air, typically sized within 10% of the exhaust volume. The reason is depressurization: a 600 CFM hood in a tight, well-sealed home can pull the house several pascals negative, backdrafting atmospherically vented water heaters and furnaces and sucking wood smoke back down the fireplace. The calculator flags every result at or above 400 CFM.

Does a range hood need a dedicated circuit?▼

Most residential hoods draw under 2 amps (a light load), but the standard installation practice — and many local codes — calls for a dedicated 15-amp, 120-volt circuit so the hood can never share a breaker with countertop appliances. Professional-grade 600+ CFM blower combinations, external inline blowers and makeup-air damper assemblies add another motor or two; plan one dedicated 15 A circuit for the hood and a second for the makeup-air damper if your installation needs one.

How many CFM does a grill hood (outdoor BBQ hood) need?▼

Outdoor grill hoods follow the pro-style math: 150 CFM per linear foot of grill is the floor, and open-air cross-breezes push real installs toward 200 CFM per linear foot. A common 42-inch (3.5 ft) built-in grill therefore wants 525–700 CFM. Depth matters more outdoors — a 24-inch-deep canopy covers the plume far better than an 18-inch one, and deeper hoods let you drop the mounting height into the 30–36 in. band where capture actually happens.

Is a higher CFM range hood always better?▼

No — past roughly 400 CFM three costs stack up: makeup air becomes a code item, heating and cooling losses climb with every minute of runtime, and noise rises steeply (a 900 CFM hood on high can top 10 sones — conversation-stopping). The right answer is a hood sized to the cooktop with a variable-speed blower: run 250–350 CFM for weeknight cooking and reserve the top speed for searing and stir-frys.

How does this page differ from the Kitchen Hood preset on the homepage?▼

The homepage calculator's Kitchen Hood preset is the quick version: 15 ACH applied to any room's volume with an 8-inch duct and safety-factor defaults. This page is the full hood-sizing decision: the linear-foot capture rule, the island and pro-style uplifts, commercial footprint sizing, the duct-size table, the 400 CFM makeup-air threshold and the dedicated-circuit question. Use the preset for a fast number; use this page when you are actually buying and installing the hood.

Related Tools & Guides

🌀

CFM to FPM Calculator

Convert CFM to FPM and FPM to CFM for any round or rectangul...

🔄

CFM Conversion Calculator

Convert CFM to m³/h, CMH, CMM, L/s, LPM, m³/s and CFH instan...

🔥

CFM to BTU Calculator

Convert CFM to BTU and BTU to CFM with the 1.08 ΔT formula —...

⚙️

Fan Performance Calculator

Calculate fan CFM from RPM with the affinity laws — static p...

☀️

Attic Fan CFM Calculator

Attic fan CFM calculator: size attic exhaust at 0.7–1.0 CFM ...

🔧

Air Compressor CFM Calculator

Air compressor CFM calculator: total your tools' CFM at 90 P...

🌡️

SCFM to CFM Calculator

SCFM to CFM calculator with pressure and temperature correct...

🌀

Blower CFM Calculator

Blower CFM calculator: size any blower from wheel diameter, ...

🌱

Grow Tent CFM Calculator

Grow tent CFM calculator: size 2×2 to 4×8 tents by air chang...

❄️

CFM per Ton Calculator

CFM per ton calculator: convert tons to CFM at 350, 400 or 4...

🪵

Dust Collector CFM Calculator

Dust collector CFM calculator: match machine CFM demands, ke...

🎨

Paint Booth CFM Calculator

Paint booth CFM calculator: size cross-draft and downdraft s...

🌫️

Air Purifier CFM Calculator

Air purifier CFM calculator: match CADR to room size with th...

💧

Evaporative Cooler CFM Calculator

Evaporative cooler CFM calculator: size swamp coolers at 20–...

🌬️

Air Handler CFM Calculator

Air handler CFM calculator: split supply vs return air, chec...

🏎️

Engine CFM Calculator

Engine CFM calculator: size carburetors from CID and RPM wit...

🌿

Greenhouse CFM Calculator

Greenhouse CFM calculator: summer cooling at one exchange pe...

🚿

Bathroom Exhaust Fan CFM Calculator

Bathroom exhaust fan CFM calculator: size by room volume at ...

🔁

Air Changes per Hour Calculator

Convert air changes per hour to CFM and back with the ACH fo...

📐

CFM to Square Feet Calculator

Turn CFM into square feet: coverage area from 700, 1500 or 3...

🏡

Whole House Fan CFM: Sizing Whole-House Fans, HRVs & ERVs

Size a whole-house fan at 2–3 CFM per sq ft or one air chang...

Size the hood before the installer does

Two methods, the duct size, and the makeup-air verdict in one pass — enter the kitchen once and take the shopping list with you.